NSN 5925-01-202-4332 of Circuit Breaker - Parts Details
Alternative NSN: 5925012024332 |
Item Name: Circuit Breaker |
FSG: 59 Electrical and Electronic Equipment Components |
Federal Supply Class (FSC): 5925 Circuit Breakers |
NIIN: 012024332 |
NCB Code: USA (01) |
Manufacturers: Vulcan Hart Corp , Eaton Corp |
ASAP Aviation Procurement, owned and operated by ASAP Semiconductor, is the latest parts procurement platform for the aerospace and aviation industry. Check out high demanding part numbers 4747, 2912-30, 2912 30AMP under NSN 5925-01-202-4332 of Circuit Breaker manufactured by Vulcan Hart Corp, Eaton Corp.
Federal Supply Class of NSN 5925-01-202-4332 is FSC 5925 contains part details of Circuit Breakers. Quote for your desired part numbers.
Part Number's List for NSN 5925-01-202-4332, 5925012024332
Characteristics Data of NSN 5925012024332MRC Criteria Characteristic AAQL BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE ADAQ BODY LENGTH 3.740 INCHES MINIMUM AND 3.760 INCHES MAXIMUM ADAT BODY WIDTH 1.970 INCHES MINIMUM AND 1.990 INCHES MAXIMUM ADAU BODY HEIGHT 2.928 INCHES MINIMUM AND 2.948 INCHES MAXIMUM ADTV CASE MATERIAL PLASTIC AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.990 INCHES MINIMUM AND 1.010 INCHES MAXIMUM AFJN FRAGILITY FACTOR MODERATELY RUGGED AJEC BOSS HEIGHT 0.053 INCHES MINIMUM AND 0.073 INCHES MAXIMUM AKPX POLE QUANTITY 2 APNQ ARC QUENCHING METHOD MAGNETIC BLOWOUT AXHR MOUNTING FACILITY TYPE AND QUANTITY 2 CLIP BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 30.0 AMPERES AC ALL LOCATIONS CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC ALL LOCATIONS CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 5000.0 AC ALL LOCATIONS CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC ALL LOCATIONS CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS CPRQ RESET METHOD MANUAL CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE CPRT MANUAL ACTUATOR TYPE AND QUANTITY 2 TOGGLE CPRW ACTUATOR FUNCTION TRIP-RESET CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE CPRY EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE AND TWO LINKED CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 1.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 3.000 MAXIMUM AT 200 PCT ALL LOCATIONS CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED DUSTPROOF AND FUNGUS PROOF FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS TTQY TERMINAL TYPE AND QUANTITY 4 COMPRESSION
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 3.740 INCHES MINIMUM AND 3.760 INCHES MAXIMUM |
ADAT | BODY WIDTH | 1.970 INCHES MINIMUM AND 1.990 INCHES MAXIMUM |
ADAU | BODY HEIGHT | 2.928 INCHES MINIMUM AND 2.948 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.990 INCHES MINIMUM AND 1.010 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.053 INCHES MINIMUM AND 0.073 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 2 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 CLIP |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 1.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 3.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 COMPRESSION |