NSN 5925-01-269-3995 of Circuit Breaker - Parts Details
Alternative NSN: 5925012693995 |
Item Name: Circuit Breaker |
FSG: 59 Electrical and Electronic Equipment Components |
Federal Supply Class (FSC): 5925 Circuit Breakers |
NIIN: 012693995 |
NCB Code: USA (01) |
Manufacturers: Westinghouse Electric Corp , Eaton Corp |
ASAP Aviation Procurement, owned and operated by ASAP Semiconductor, is the latest parts procurement platform for the aerospace and aviation industry. Check out high demanding part numbers XFB3040PLV, FB3040PLV under NSN 5925-01-269-3995 of Circuit Breaker manufactured by Westinghouse Electric Corp, Eaton Corp.
Federal Supply Class of NSN 5925-01-269-3995 is FSC 5925 contains part details of Circuit Breakers. Quote for your desired part numbers.
Part Number's List for NSN 5925-01-269-3995, 5925012693995
-
Part No Manufacturer Item Name QTY RFQ XFB3040PLV Westinghouse Electric Corp circuit breaker Avl RFQ FB3040PLV Eaton Corp circuit breaker Avl RFQ
Characteristics Data of NSN 5925012693995MRC Criteria Characteristic AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE ADAQ BODY LENGTH 6.000 INCHES NOMINAL ADAT BODY WIDTH 4.125 INCHES NOMINAL ADAU BODY HEIGHT 3.375 INCHES NOMINAL ADTV CASE MATERIAL PLASTIC AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 5.062 INCHES NOMINAL AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.375 INCHES NOMINAL AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.188 INCHES NOMINAL AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 4.500 INCHES NOMINAL AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.375 INCHES NOMINAL AFJN FRAGILITY FACTOR MODERATELY RUGGED AJEC BOSS HEIGHT 0.125 INCHES NOMINAL AKPX POLE QUANTITY 3 APNQ ARC QUENCHING METHOD MAGNETIC BLOWOUT AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 UNTHREADED HOLE BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 40.0 AMPERES AC ALL LOCATIONS CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 600.0 AC ALL LOCATIONS CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 200000.0 AC ALL LOCATIONS CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS CPRQ RESET METHOD MANUAL CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE CPRW ACTUATOR FUNCTION TRIP-RESET CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 30.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 85.000 MAXIMUM AT 200 PCT ALL LOCATIONS CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT CRCF TRIP RELEASE AMBIENT TEMP RATING 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS FEAT SPECIAL FEATURES WITH LUGS FURNISHED FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS TTQY TERMINAL TYPE AND QUANTITY 6 COMPRESSION
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 6.000 INCHES NOMINAL |
ADAT | BODY WIDTH | 4.125 INCHES NOMINAL |
ADAU | BODY HEIGHT | 3.375 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.062 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.188 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.500 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.125 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 200000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 30.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 85.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FEAT | SPECIAL FEATURES | WITH LUGS FURNISHED |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |