TED124040 by General Electric Company with NSN 5925010228122 - Submit a Quote
Part No. : TED124040 | Manufacturer : General Electric Company | NSN : 5925-01-022-8122 |
Item Name : Circuit Breaker | CAGE Code : 60969 | FSC : 5925 Circuit Breakers |
ASAP Aviation Procurement is pleased to announce that part number TED124040 of NSN 5925010228122 is now available and in stock. We can get you one of the fastest and most competitive quotes on this part. Part number TED124040 is a circuit breaker manufactured by general electric company under CAGE Code 60969. Simply fill out the Request for Quote (RFQ) form provided here to get started on your quote.In order to make sure that we get you your quote in a timely manner, please take the time to make sure that all fields are completely filled out, particularly the asterisk-marked (*) fields like Parts Needed By and Quantity (ea).
We will be using your response to these fields to calculate your quote. Within 15 minutes of receiving your RFQ, a member of our sales team will contact you with your quote. ASAP Aviation Procurement, owned and operated by ASAP Semiconductor, is a leading distributor of new and obsolete NSN parts for the aerospace, civil aviation, and defense industries. With our inventory of more than 2 billion parts sourced from over 5000 manufacturers from around the world, we do our level best to become your go-to one-stop shop. And to help us offer you the best streamlined parts procurement experience, we have advanced shipping facilities across USA. TED124040 general electric company is in stock.
Are you interested in learning more about part number TED124040? If so, feel free to contact us by phone at +1-714-705-4780, or by email at sales@asap-aviationprocurement.com. And if you are interested in an even faster and more convenient purchasing platform, check out the ASAP Semiconductor App from Google Play or the App Store.
NSN Information for Part Number TED124040 with NSN 5925-01-022-8122, 5925010228122
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-022-8122 Item Description: CIRCUIT BREAKER | 5925 | 010228122 | P | |||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
TED124040 | 5 | 2 | 3 |
Characteristics Data of NSN 5925-01-022-8122, 5925010228122MRC Criteria Characteristic AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE ADAQ BODY LENGTH 6.312 INCHES NOMINAL ADAT BODY WIDTH 2.750 INCHES NOMINAL ADAU BODY HEIGHT 3.140 INCHES NOMINAL ADTV CASE MATERIAL PLASTIC AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 4.620 INCHES NOMINAL AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.380 INCHES NOMINAL AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 4.620 INCHES NOMINAL AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.375 INCHES NOMINAL AFJN FRAGILITY FACTOR MODERATELY RUGGED AJEC BOSS HEIGHT 0.710 INCHES NOMINAL AKPX POLE QUANTITY 2 APNQ ARC QUENCHING METHOD AIR AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 UNTHREADED HOLE BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE CBME III CUBIC MEASURE 55.314 CUBIC INCHES CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 40.0 AMPERES AC ALL LOCATIONS AND 40.0 AMPERES DC ALL LOCATIONS CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 480.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 18000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS CPRQ RESET METHOD MANUAL CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE CPRW ACTUATOR FUNCTION TRIP-RESET CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 725.000 MINIMUM AT 100 PCT ALL LOCATIONS AND 1000.000 MAXIMUM AT 100 PCT ALL LOCATIONS AND 30.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 125.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 15.000 MINIMUM AT 250 PCT ALL LOCATIONS AND 60.000 MAXIMUM A CRCF TRIP RELEASE AMBIENT TEMP RATING 10.0 DEG CELSIUS MINIMUM ALL LOCATIONS AND 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS TTQY TERMINAL TYPE AND QUANTITY 4 SCREW
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 6.312 INCHES NOMINAL |
ADAT | BODY WIDTH | 2.750 INCHES NOMINAL |
ADAU | BODY HEIGHT | 3.140 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.620 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.380 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.620 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.710 INCHES NOMINAL |
AKPX | POLE QUANTITY | 2 |
APNQ | ARC QUENCHING METHOD | AIR |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CBME | III CUBIC MEASURE | 55.314 CUBIC INCHES |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES AC ALL LOCATIONS AND 40.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 725.000 MINIMUM AT 100 PCT ALL LOCATIONS AND 1000.000 MAXIMUM AT 100 PCT ALL LOCATIONS AND 30.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 125.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 15.000 MINIMUM AT 250 PCT ALL LOCATIONS AND 60.000 MAXIMUM A |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 10.0 DEG CELSIUS MINIMUM ALL LOCATIONS AND 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 SCREW |