NSN 5925-00-933-6041 of Circuit Breaker - Parts Details
Alternative NSN: 5925009336041 |
Item Name: Circuit Breaker |
FSG: 59 Electrical and Electronic Equipment Components |
Federal Supply Class (FSC): 5925 Circuit Breakers |
NIIN: 009336041 |
NCB Code: USA (00) |
Manufacturers: Eaton Corp , Wood Electric Operations Potter And Brumfield , Eastman Kodak Company |
ASAP Aviation Procurement, owned and operated by ASAP Semiconductor, is the latest parts procurement platform for the aerospace and aviation industry. Check out high demanding part numbers AM33MG6-30-250-60CYC4, AM33MG6-30-250-4-60, AM33-30-250VAC60C4, 190-230-101, 037-225 under NSN 5925-00-933-6041 of Circuit Breaker manufactured by Eaton Corp, Wood Electric Operations Potter And Brumfield, Eastman Kodak Company.
Federal Supply Class of NSN 5925-00-933-6041 is FSC 5925 contains part details of Circuit Breakers. Quote for your desired part numbers.
Part Number's List for NSN 5925-00-933-6041, 5925009336041
-
Part No Manufacturer Item Name QTY RFQ AM33MG6-30-250-60CYC4 Eaton Corp circuit breaker Avl RFQ AM33MG6-30-250-4-60 Eaton Corp circuit breaker Avl RFQ AM33-30-250VAC60C4 Eaton Corp circuit breaker Avl RFQ 190-230-101 Wood Electric Operations Potter And Brumfield circuit breaker Avl RFQ 037-225 Eastman Kodak Company circuit breaker Avl RFQ
Characteristics Data of NSN 5925009336041MRC Criteria Characteristic CQXF Inclosure Protection Type For Which Designed EXPLOSION RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANT AEBY Distance Between Centerlines Of Mounting Facilities Parallel To Body Length 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM BBRG Storage Type GENERAL PURPOSE WAREHOUSE CPLM Maximum Continuous Load Current Rating Per Pole 30.0 AMPERES AC ALL LOCATIONS AKPX Pole Quantity 2 CPRF Operating Voltage Type And Rating Per Pole In Volts 250.0 AC ALL LOCATIONS CPRH Circuit Protection Type OVERCURRENT ALL LOCATIONS AFJN Fragility Factor MODERATELY RUGGED CPRJ Trip Release Method MAGNETIC-HYDRAULIC ALL LOCATIONS FREQ Frequency In Hertz 60.0 ALL LOCATIONS AJEC Boss Height 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM CPRN Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent 150.0 ALL LOCATIONS CPRL Trip Release Characteristic TIME DELAY ALL LOCATIONS AEHA Distance Between Centerlines Of Mounting Facilities Parallel To Body Width 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM CPRR Main Contact Tripping Mechanism Type TRIP FREE ADAT Body Width 1.490 INCHES MINIMUM AND 1.510 INCHES MAXIMUM TTQY Terminal Type And Quantity 4 THREADED STUD THSD Thread Series Designator UNC CPRX Actuator Position Designation AT EACH POLE CPRT Manual Actuator Type And Quantity 2 TOGGLE CPSM Internal Trip Release Configuration SERIES TRIP ALL LOCATIONS CPRW Actuator Function TRIP-RESET CQJX Nominal Thread Size 0.138 INCHES AXHR Mounting Facility Type And Quantity 4 THREADED HOLE ADTV Case Material PLASTIC AJWX Mounting Surface To Terminal End Distance 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM ADAQ Body Length 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM AEBP Center To Center Distance Between Terminals Parallel To Length 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM AAQL Body Style MULTIPOLE-MULTIPLE ACTUATOR TYPE AEBQ Center To Center Distance Between Terminals Parallel To Width 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM APNQ Arc Quenching Method AIR CMLP Thread Quantity Per Inch 32 CPRG Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps 1000.0 AC ALL LOCATIONS CQWN Trip Delay Time In Seconds Per Rated Continuous Current 4.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 11.000 MAXIMUM AT 200 PCT ALL LOCATIONS CPRQ Reset Method MANUAL MRC Decoded Requirement Clear Text Reply CPRY External Actuator Linkage Arrangement ONE AND TWO LINKED
MRC | Criteria | Characteristic |
---|---|---|
CQXF | Inclosure Protection Type For Which Designed | EXPLOSION RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANT |
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
BBRG | Storage Type | GENERAL PURPOSE WAREHOUSE |
CPLM | Maximum Continuous Load Current Rating Per Pole | 30.0 AMPERES AC ALL LOCATIONS |
AKPX | Pole Quantity | 2 |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 250.0 AC ALL LOCATIONS |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
AFJN | Fragility Factor | MODERATELY RUGGED |
CPRJ | Trip Release Method | MAGNETIC-HYDRAULIC ALL LOCATIONS |
FREQ | Frequency In Hertz | 60.0 ALL LOCATIONS |
AJEC | Boss Height | 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 150.0 ALL LOCATIONS |
CPRL | Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
AEHA | Distance Between Centerlines Of Mounting Facilities Parallel To Body Width | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
ADAT | Body Width | 1.490 INCHES MINIMUM AND 1.510 INCHES MAXIMUM |
TTQY | Terminal Type And Quantity | 4 THREADED STUD |
THSD | Thread Series Designator | UNC |
CPRX | Actuator Position Designation | AT EACH POLE |
CPRT | Manual Actuator Type And Quantity | 2 TOGGLE |
CPSM | Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
CPRW | Actuator Function | TRIP-RESET |
CQJX | Nominal Thread Size | 0.138 INCHES |
AXHR | Mounting Facility Type And Quantity | 4 THREADED HOLE |
ADTV | Case Material | PLASTIC |
AJWX | Mounting Surface To Terminal End Distance | 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM |
ADAQ | Body Length | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
AAQL | Body Style | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
AEBQ | Center To Center Distance Between Terminals Parallel To Width | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
APNQ | Arc Quenching Method | AIR |
CMLP | Thread Quantity Per Inch | 32 |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 1000.0 AC ALL LOCATIONS |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 4.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 11.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRQ | Reset Method | MANUAL |
MRC | Decoded Requirement | Clear Text Reply |
CPRY | External Actuator Linkage Arrangement | ONE AND TWO LINKED |