XAM333-45-208VAC60-1 by Eaton Corp with NSN 5925008169929 - Submit a Quote
Part No. : XAM333-45-208VAC60-1 | Alternate P/N: XAM33345208VAC601 | Manufacturer : Eaton Corp | NSN : 5925-00-816-9929 |
Item Name : Circuit Breaker | CAGE Code : 74193 | FSC : 5925 Circuit Breakers |
ASAP Aviation Procurement is pleased to announce that part number XAM333-45-208VAC60-1 of NSN 5925008169929 is now available and in stock. We can get you one of the fastest and most competitive quotes on this part. Part number XAM333-45-208VAC60-1 is a circuit breaker manufactured by eaton corp under CAGE Code 74193. Simply fill out the Request for Quote (RFQ) form provided here to get started on your quote.In order to make sure that we get you your quote in a timely manner, please take the time to make sure that all fields are completely filled out, particularly the asterisk-marked (*) fields like Parts Needed By and Quantity (ea).
We will be using your response to these fields to calculate your quote. Within 15 minutes of receiving your RFQ, a member of our sales team will contact you with your quote. ASAP Aviation Procurement, owned and operated by ASAP Semiconductor, is a leading distributor of new and obsolete NSN parts for the aerospace, civil aviation, and defense industries. With our inventory of more than 2 billion parts sourced from over 5000 manufacturers from around the world, we do our level best to become your go-to one-stop shop. And to help us offer you the best streamlined parts procurement experience, we have advanced shipping facilities across USA. XAM333-45-208VAC60-1 eaton corp is in stock.
Are you interested in learning more about part number XAM333-45-208VAC60-1? If so, feel free to contact us by phone at +1-714-705-4780, or by email at sales@asap-aviationprocurement.com. And if you are interested in an even faster and more convenient purchasing platform, check out the ASAP Semiconductor App from Google Play or the App Store.
NSN Information for Part Number XAM333-45-208VAC60-1 with NSN 5925-00-816-9929, 5925008169929
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-816-9929 Item Description: CIRCUIT BREAKER | 5925 | 008169929 | P | |||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
XAM333-45-208VAC60-1 | 2 | 9 | 5 |
Characteristics Data of NSN 5925-00-816-9929, 5925008169929MRC Criteria Characteristic AAQL BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE ADAQ BODY LENGTH 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM ADAT BODY WIDTH 2.240 INCHES MINIMUM AND 2.260 INCHES MAXIMUM AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 2.689 INCHES MINIMUM AND 2.813 INCHES MAXIMUM AKPX POLE QUANTITY 3 AXHR MOUNTING FACILITY TYPE AND QUANTITY 6 THREADED HOLE BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE CMLP THREAD QUANTITY PER INCH 32 CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 45.0 AMPERES AC ALL LOCATIONS CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 208.0 AC ALL LOCATIONS CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC ALL LOCATIONS CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS CPRP ULTIMATE TRIP TIME PER POLE IN SECONDS 18.000 MINIMUM ALL LOCATIONS AND 70.000 MAXIMUM ALL LOCATIONS CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE CPRW ACTUATOR FUNCTION TRIP-RESET CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE CQJX NOMINAL THREAD SIZE 0.138 INCHES CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 10.000 MINIMUM AT 150 PCT ALL LOCATIONS AND 30.000 MAXIMUM AT 150 PCT ALL LOCATIONS AND 4.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 10.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 1.400 MINIMUM AT 300 PCT ALL LOCATIONS AND 4.000 MAXIMUM AT 300 P CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT AND MOISTURE RESISTANT AND EXPLOSION RESISTANT FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS THSD THREAD SERIES DESIGNATOR UNC TTQY TERMINAL TYPE AND QUANTITY 3 SCREW ADTV CASE MATERIAL PLASTIC AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM AFJN FRAGILITY FACTOR MODERATELY RUGGED AJEC BOSS HEIGHT 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM APNQ ARC QUENCHING METHOD MAGNETIC BLOWOUT CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS CPRQ RESET METHOD MANUAL CPRY EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE, TWO, AND THREE LINKED CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
ADAT | BODY WIDTH | 2.240 INCHES MINIMUM AND 2.260 INCHES MAXIMUM |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.689 INCHES MINIMUM AND 2.813 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 45.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 208.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 18.000 MINIMUM ALL LOCATIONS AND 70.000 MAXIMUM ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 150 PCT ALL LOCATIONS AND 30.000 MAXIMUM AT 150 PCT ALL LOCATIONS AND 4.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 10.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 1.400 MINIMUM AT 300 PCT ALL LOCATIONS AND 4.000 MAXIMUM AT 300 P |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT AND EXPLOSION RESISTANT |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 3 SCREW |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
Related NSN Components For XAM333-45-208VAC60-1
Industry's fastest RFQ turnaround. Get the answers you need now.
E-mail us at
sales@asap-aviationprocurement.com